Mixture, Ignitable (Flammable)

Mixture, Ignitable (Flammable)

Definition(s)


Mixture, ignitable (flammable)

A gas-air mixture that is capable of being ignited by an open flame, electric arc or spark or high temperature. See explosive limits. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Location Not Requiring an Exceptional Degree of Protection

Location Not Requiring an Exceptional Degree of Protection

Definition(s)


Location not requiring an exceptional degree of protection

A location that is not exposed to the environmental conditions outlined in the definition of 3.3.9. These locations include: a) accommodation spaces such as quarters buildings, b) dry store rooms, and c) other locations with similar environmental conditions. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Nonincendive Field Wiring

Nonincendive Field Wiring

Definition(s)


Nonincendive Field Wiring

Wiring that enters or leaves an equipment enclosure and, under normal operating conditions of the equipment, is not capable, due to arcing or thermal effects, of igniting the flammable gas-, vapor-, or dust-air mixture. Normal operation includes opening, shorting, or grounding the field wiring, See also nonincendive circuit. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Nonincendive Equipment

Nonincendive Equipment

Definition(s)


Nonincendive equipment

Equipment having electrical/electronic circuitry and components that are incapable, under normal conditions, of causing ignition of the flammable gas-, vapor-, or dust-air mixture due to arcing or thermal effect. Such devices may be incorporated into equipment having the types of protection referred to as "nA," "nC," or "nR." Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Nonincendive Component

Nonincendive Component

Definition(s)


Nonincendive component

A component having contacts for making or breaking an incendive circuit, and the contacting mechanism is constructed so that the component is incapable of igniting the specified flammable gas or vapor-air mixture. The housing of a nonincendive component is not intended to exclude the flammable atmosphere or contain an explosion. Such devices may be incorporated into equipment having the type of protection referred to as "nC." Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Nonincendive Circuit

Nonincendive Circuit

Definition(s)


Nonincendive circuit

A circuit, other than field wiring, in which any arc or thermal effect produced, under intended operating conditions of the equipment, is not capable, under specified test conditions, of igniting the flammable gas-, vapor-, or dust-air mixture. See also nonincendive field wiring. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
MODU

MODU

Definition(s)


MODU

Mobile offshore drilling unit. Source: API RP 2D, Operation and Maintenance of Offshore Cranes, Seventh Edition, December 2014. Global Standards Source: API  Bulletin 97, Well Construction Interface Document Guidelines, First Edition, December 2013. Global Standards Source: A Guide to the Offshore Installations and Pipelines Works (Management and Administration) Regulations 1995, Guidance on Regulations (UK HSE L70), Second Edition, 2002. Regulatory Guidance  Source: API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards Source: API RP 14G, Recommended Practice for Fire Prevention and Control on Fixed Open-type Offshore Production Platforms: Upstream Segment, Fourth Edition, April 2007. Global Standards Source: API SPEC 7K, Drilling and Well Servicing Equipment Upstream Segment, Fifth Edition, June 2010 (August 2010). Global Standards Source:API SPECIFICATION 7K, Drilling and Well Servicing Equipment, Sixth Edition, December 2015. Global Standards Source: Environmental Protection Plan Guidelines, The Canada-Newfoundland and Labrador Offshore Petroleum Board, Canada-Nova Scotia Offshore Petroleum Board, and National Energy Board, Canada, March 31, 2011. Regulatory Guidance Source: Incident Reporting and Investigation Guidelines, The Canada-Nova Scotia Offshore Petroleum Board and Canada-Newfoundland and Labrador Offshore Petroleum Board, Canada, November 30, 2012. Regulatory Guidance Source: NOPSEMA Guidance Note: ALARP, N-04300-GN0166, Australia, Revision 4, December 2012. Regulatory Guidance Source: NOPSEMA Guidance Note: Control Measures and Performance Standards, N-04300 GN0271, Australia, Revision 3, December 2011. Regulatory Guidance Source: International Association of Drilling Contractors, Appendix 2 to Health, Safety and Environment Case Guidelines for Offshore Drilling Contractors, Issue 3.3.2, February 2010. IADC Guidelines Source: ISO 19901-7:2013, Petroleum and natural gas industries – Specific requirements for offshore structures – Part 7: Stationkeeping systems for floating offshore structures and mobile offshore units. Global Standards Source: Rules for Classification and Construction, IV Industrial Services, 6 Offshore Technology, 9 Guideline for Personnel Transfers by Means of Lifting Appliances, Edition 2011, Germanischer Lloyd SE, Global Standards Source: Safety Plan Guidelines, The Canada-Newfoundland and Labrador Offshore Petroleum Board, Canada-Nova Scotia Offshore Petroleum Board, and National Energy Board, Canada, March 31, 2011. Regulatory Guidance  

MODU

Structure capable of engaging in drilling and well intervention operations for exploration or exploitation of subsea petroleum resources. Source: ISO 19901-7:2013, Petroleum and natural gas industries – Specific requirements for offshore structures – Part 7: Stationkeeping systems for floating offshore structures and mobile offshore units. Global Standards  

MODU

Mobile offshore drilling unit. Requirements for MODU will also be applicable for floating production and drilling units. Source: NORSOK D-001, Drilling facilities, Rev. 3, December 2012. Global Standards
Zone

Zone

Definition(s)


Zone

A method of specifying the probability that a location is made hazardous by the presence, or potential presence, of flammable concentrations of gases and vapors, or combustible mixtures of dusts. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Zone 0 (IEC)

An area in which an explosive gas atmosphere is present continuously or for long periods. (See IEC 60050, IEV 426-03-03.) Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Zone 0, Class I (NEC)

A Class I, Zone 0 location is a location 1) in which ignitable concentrations of flammable gases or vapors are present continuously; or 2) in which ignitable concentrations of flammable gases or vapors are present for long periods of time, see NEC Section 505.5(B)(1). Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards  

Zone 0, Class I (NEC)

A Class I, Zone 0 location is a location 1) in which ignitable concentrations of flammable gases or vapors are present continuously; or 2) in which ignitable concentrations of flammable gases or vapors are present for long periods of time, see NEC Section 505-9(a). Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Zone 0

Place in which an explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist is present continuously or for long periods or frequently.[IEV 426-03-03, modified] NOTE The MODU code definition is “Zone 0: in which an explosive gas/air mixture is continuously present or present for long periods.” Source: IEC 61892-7, Mobile and fixed offshore units – Electrical installations – Part 7: Hazardous areas. Global Standards  

Zone 1 (IEC)

An area in which an explosive gas atmosphere is likely to occur in normal operation, see IEC 60050, IEV 426-03-04. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Zone 1, Class I (NEC)

A Class I, Zone 1 location is a location 1) in which ignitable concentrations of flammable gases or vapors are likely to exist under normal operating conditions; or 2) in which ignitable concentrations of flammable gases or vapors may exist frequently because of repair or maintenance operations or because of leakage; or 3) in which equipment is operated or processes are carried on, of such a nature that equipment breakdown or faulty operations could result in the release of ignitable concentrations of flammable gases or vapors and also cause simultaneous failure of electrical equipment in a mode to cause the electrical equipment to become a source of ignition; or 4) that is adjacent to a Class I, Zone 0 location from which ignitable concentrations of vapors could be communicated, unless communication is prevented by adequate positive-pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided, see NEC Article 505.5(B)(2). Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards  

Zone 1, Class I (NEC)

A Class I, Zone 1 location is a location 1) in which ignitable concentrations of flammable gases or vapors are likely to exist under normal operating conditions; or 2) in which ignitable concentrations of flammable gases or vapors may exist frequently because of repair or maintenance operations or because of leakage; or 3) in which equipment is operated or processes are carried on, of such a nature that equipment breakdown or faulty operations could result in the release of ignitable concentrations of flammable gases or vapors and also cause simultaneous failure of electrical equipment in a mode to cause the electrical equipment to become a source of ignition; or 4) that is adjacent to a Class I, Zone 0 location from which ignitable concentrations of vapors could be communicated, unless communication is prevented by adequate positive-pressure ventilation from a source of clean air and effective safeguards against ventilation failure are provided, see NEC Article 505-9(b). Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Zone 1

Place in which an explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist is likely to occur in normal operation occasionally. [IEV 426-03-04, modified] NOTE The MODU code definition is “Zone 1: in which an explosive gas/air mixture is likely to occur in normal operation.” Source: IEC 61892-7, Mobile and fixed offshore units – Electrical installations – Part 7: Hazardous areas. Global Standards  

Zone 2 (IEC)

An area in which an explosive gas atmosphere is not likely to occur in normal operation and, if it does occur, is likely to do so only infrequently and will exist for a short period only, see IEC 60050, IEV 426-03-05. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Zone 2, Class I (NEC)

A Class I, Zone 2 location is a location 1) in which ignitable concentrations of flammable gases or vapors are not likely to occur in normal operation, and if they do occur, will exist only for a short period; or 2) in which volatile flammable liquids, flammable gases, or flammable vapors are handled, processed, or used, but in which the liquids, gases, or vapors normally are confined within closed containers or closed systems from which they can escape only as a result of accidental rupture or breakdown of the containers or system, or as the result of the abnormal operation of the equipment with which the liquids or gases are handled, processed, or used; or 3) in which ignitable concentrations of flammable gases or vapors normally are prevented by positive mechanical ventilation, but which may become hazardous as the result of failure or abnormal operation of the ventilation equipment; or 4) that is adjacent to a Class I, Zone 1 location, from which ignitable concentrations of flammable gases or vapors could be communicated, unless such communication is prevented by adequate positive-pressure ventilation from a source of clean air, and effective safeguards against ventilation failure are provided, see NEC Section 505.5(B)(3). Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards  

Zone 2, Class I (NEC)

A Class I, Zone 2 location is a location 1) in which ignitable concentrations of flammable gases or vapors are not likely to occur in normal operation, and if they do occur, will exist only for a short period; or 2) in which volatile flammable liquids, flammable gases, or flammable vapors are handled, processed, or used, but in which the liquids, gases, or vapors normally are confined within closed containers or closed systems from which they can escape only as a result of accidental rupture or breakdown of the containers or system, or as the result of the abnormal operation of the equipment with which the liquids or gases are handled, processed, or used; or 3) in which ignitable concentrations of flammable gases or vapors normally are prevented by positive mechanical ventilation, but which may become hazardous as the result of failure or abnormal operation of the ventilation equipment; or 4) that is adjacent to a Class I, Zone 1 location, from which ignitable concentrations of flammable gases or vapors could be communicated, unless such communication is prevented by adequate positive-pressure ventilation from a source of clean air, and effective safeguards against ventilation failure are provided, see NEC Section 505-9(c). Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Zone 2

Place in which an explosive atmosphere consisting of a mixture with air of flammable substances in the form of gas, vapour or mist is not likely to occur in normal operation but, if it does occur, will persist for a short period only.[IEV 426-03-05, modified] NOTE 1 In this definition, the word "persist" means the total time for which the flammable atmosphere will exist. This will normally comprise the total of the duration of the release, plus the time taken for the flammable atmosphere to disperse after the release has stopped. NOTE 2 Indications of the frequency of the occurrence and duration may be taken from codes relating to specific industries or applications. NOTE 3 The MODU code definition is “Zone 2: in which an explosive gas/air mixture is not likely to occur, or in which such a mixture, if it does occur, will only exist for a short time.”3  

Zone

“Zone” means any stratum or strata designated by the Minister as a zone, either generally or in respect of any designated area, or any specified well or wells (zone). Source: Canada Oil and Gas Drilling and Production Regulations, C.R.C., c. 1517, February 2013. Regulations  

Zone

“Zone” means any stratum or any sequence of strata and includes, for the purposes of the definition “commingled production”, section 7, subsection 61(2), sections 64 to 66 and 73, subsection 82(2) and section 85, a zone that has been designated as such by the Board under section 4 (couche). Source: Canada Oil and Gas Drilling and Production Regulations, SOR/2009-315, February 2013. Regulations Source: Drilling and Production Guidelines, The Canada-Nova Scotia Offshore Petroleum Board and Canada-Newfoundland and Labrador Offshore Petroleum Board, Canada, March 31, 2011. Regulatory Guidance  

Zone

Part of a hazardous area based upon the frequency of the occurrence and duration of an explosive gas atmosphere. Source: ISO 13702:2015, Petroleum and natural gas industries — Control and mitigation of fires and explosions on offshore production installations — Requirements and guidelines, Second Edition, August 2015. Global Standards  

Zone

“Zone” means any stratum or any sequence of strata and includes, for the purposes of the definition “commingled production”, section 7, subsection 61(2), sections 64 to 66 and 74, subsection 83(2) and section 86, a zone that has been designated as such by the Board under section 4; couche. Source: Nova Scotia Offshore Petroleum Drilling and Production Regulations, SOR/2009-317, Canada, current to May 31, 2012. Regulations  

Zone

See “security zone

Source: ANSI/ISA–99.00.01–2007, Security for Industrial Automation and Control Systems, Part 1: Terminology, Concepts, and Models, 29 October 2007. National Standard
Nonclassified Location

Nonclassified Location

Definition(s)


Unclassified location

An unclassified location is a location not classified as Division 1 or Division 2, or Zone 0, Zone 1, or Zone 2. NOTE: Within this document, the term unclassified location is used synonymously with the term nonclassified location. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Unclassified Location

Unclassified Location

Definition(s)


Unclassified location

An unclassified location is a location not classified as Division 1 or Division 2, or Zone 0, Zone 1, or Zone 2.
  • NOTE: Within this document, the term unclassified location is used synonymously with the term nonclassified location.
Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Ventilation

Ventilation

Definition(s)


Ventilation, adequate

Ventilation (natural or artificial) that is sufficient to prevent the accumulation of significant quantities of vapor-air mixtures in concentrations above 25 % of their lower flammable (explosive) limit, LFL (LEL). See 6.3.2 of API 500 or 6.6.2 of API 505, as applicable. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Ventilation, inadequate

Ventilation that is less than adequate. See 6.3.3 of API 500 or 6.6.3 of API 505, as applicable. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Inadequately ventilated

Ventilation (natural or artificial) that is not sufficient to prevent the accumulation of significant quantities of toxic or inert gases such that a hazard is created. Source: API RP 49, Recommended Practice for Drilling and Well Servicing Operations Involving Hydrogen Sulfide, Third Edition, May 2001. Global Standards  

Adequate ventilation

Adequate ventilation, as used in this document, is for the prevention of fire and explosions. Adequate ventilation is ventilation (natural or artificial) that is sufficient to prevent the accumulation of significant quantities of vapor-air mixtures in concentrations above 10% of their lower explosive limit (LEL). Source: API RP 54, Recommended Practice for Occupational Safety for Oil and Gas Well Drilling and Servicing Operations, Third Edition, August 1999 (2007). Global Standards  

Adequate ventilation

Adequate ventilation is for the prevention of fire and explosions. Adequate ventilation is ventilation (natural or artificial) that is sufficient to prevent the accumulation of significant quantities of vapor-air mixtures in concentrations above 10% of their lower explosive limit (LEL). Source: API RP 74, Recommended Practice for Occupational Safety for Onshore Oil and Gas Production Operation, First Edition, October 2001 (March 2007). Global Standards  

Ventilation, adequate

Ventilation (natural or artificial) that is sufficient to prevent the accumulation of significant quantities of vapor-air mixtures in concentrations above 25% of their lower flammable (explosive) limit (LFL). Source: API RP 14G, Recommended Practice for Fire Prevention and Control on Fixed Open-type Offshore Production Platforms: Upstream Segment, Fourth Edition, April 2007. Global Standards  

Ventilation, inadequate

Ventilation that is less than adequate. Source: API RP 14G, Recommended Practice for Fire Prevention and Control on Fixed Open-type Offshore Production Platforms: Upstream Segment, Fourth Edition, April 2007. Global Standards  

Ventilation

movement of air and its replacement with fresh air due to the effects of wind, temperature gradients, or artificial means (for example, fans or extractors). Source: IEC 61892-7, Mobile and fixed offshore units – Electrical installations – Part 7: Hazardous areas. Global Standards  
Source of Release

Source of Release

Definition(s)


Source of Release

A point or location from which a flammable gas, vapor, or liquid may be released into the atmosphere such that an ignitable gas atmosphere could be formed. API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards

Source of Release

A point from which flammable gases or vapors, flammable liquid, combustible dusts, or ignitable fibers or flyings may be released into the atmosphere. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Source of Release

Point or location from which a flammable gas, vapour, or liquid may be released into the atmosphere in such a way that an explosive gas atmosphere could be formed [IEV 426-03-06, modified]. Source: IEC 61892-7, Mobile and fixed offshore units – Electrical installations – Part 7: Hazardous areas. Global Standards
Seal

Seal

Definition(s)


Seal

Component designed to prevent the passage of fluids. Source: API Standard 2RD, Dynamic Risers for Floating Production Systems, Second Edition, September 2013. Global Standards

Seal

A device or approved method used to prevent tampering with royalty measurement components. Source: Oil and Gas and Sulphur Operations in the Outer Continental Shelf, 30 CFR 250 (2013). Regulations  

Seal

Barrier to prevent the passage of fluids. Source: API RP 5C5, Recommended Practice on Procedures for Testing Casing and Tubing Connections, Third Edition, July 2003 (Reaffirmed August 2010). Global Standards Source: API RP 17G, Recommended Practice for Completion/Workover Risers, Second Edition, July 2006 (Reaffirmed April 2011). Global Standards  

Seal

Device providing a barrier to the passage of liquid and/or gas. Source: API SPEC 11D1, Packers and Bridge Plugs, Upstream Segment, Second Edition, July 2009. Global Standards
Pressurization

Pressurization

Definition(s)


Pressurization

The technique of guarding against the ingress of the external atmosphere into an enclosure by maintaining a protective gas therein at a pressure above that of the external atmosphere. This type of protection is referred to as "p." Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Pressurization, Type X

A method of reducing the classification within an enclosure from Division 1/Zone 1 to nonhazardous (unclassified). Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Pressurization, Type Y

A method of reducing the classification within an enclosure from Division 1/Zone 1 to Division 2/Zone 2. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Pressurization, Type Z

A method of reducing the classification within an enclosure from Division 2/Zone 2 to nonhazardous (unclassified). Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
PVC

PVC

Definition(s)


PVC

Polyvinyl chloride. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards Source: API RP 17B, Recommended Practice for Flexible Pipe, Fourth Edition, July 2008. Global Standards Source: API SPEC 17J, Specification for Unbonded Flexible Pipe, Third Edition, July 2008. Global Standards Source: API RP 98, Personal Protective Equipment Selection for Oil Spill Responders, First Edition, August 2013. Global Standards Source: ISO 21457:2010, Petroleum and natural gas industries — Materials selection and corrosion control for oil and gas production systems, First Edition,September 2010. Global Standards  

PVC

“PVC” means poly vinyl chloride. Source: Oil and Gas, New Mexico Administrative Code Title 19, Chapter 15, January 2013. Regulations
PE

PE

Definition(s)


PE

Polyethylene. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards Source: API RP 17B, Recommended Practice for Flexible Pipe, Fourth Edition, July 2008. Global Standards Source: ISO 21457:2010, Petroleum and natural gas industries — Materials selection and corrosion control for oil and gas production systems, First Edition,September 2010. Global Standards  

PE

Unthreaded pipe either upset or non-upset. Source: API SPEC 5CT, Specification for Casing and Tubing, Upstream Segment, Ninth Edition, July 2011 (Errata September 2012). Global Standards Source: API SPEC 17J, Specification for Unbonded Flexible Pipe, Third Edition, July 2008. Global Standards
PA

PA

Definition(s)


PA

Public Address. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards Source: International Association of Drilling Contractors, Appendix 2 to Health, Safety and Environment Case Guidelines for Offshore Drilling Contractors, Issue 3.3.2, February 2010. IADC Guidelines Source: ISO 13702:2015, Petroleum and natural gas industries — Control and mitigation of fires and explosions on offshore production installations — Requirements and guidelines, Second Edition, August 2015. Global Standards  

PA

Polyamide. Source: API RP 17B, Recommended Practice for Flexible Pipe, Fourth Edition, July 2008. Global Standards Source: API SPEC 17J, Specification for Unbonded Flexible Pipe, Third Edition, July 2008. Global Standards
Oil Sealed

Oil Sealed

Definition(s)


Oil sealed

See equipment, oil immersed. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Oil-resistant

Oil-resistant

Definition(s)


Oil-resistant

Ability to withstand exposure to oil as defined by ANSI C-33.80, see UL Std 83. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
OA

OA

Definition(s)


OA

Open air. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
NRTL

NRTL

Definition(s)


NRTL

Nationally Recognized Testing Laboratory. API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards Source: API RP 14G, Recommended Practice for Fire Prevention and Control on Fixed Open-type Offshore Production Platforms: Upstream Segment, Fourth Edition, April 2007. Global Standards Source: API RP 49, Recommended Practice for Drilling and Well Servicing Operations Involving Hydrogen Sulfide, Third Edition, May 2001. Global Standards  
NFPA

NFPA

Definition(s)


NFPA

National Fire Protection Association Source: API STD 521, Pressure-relieving and Depressuring Systems, Sixth Edition, January 2014. Global Standards Source: API RP 2FB, Recommended Practice for the Design of Offshore Facilities Against Fire and Blast Loading, First Edition, April 2006. Global Standards. API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards Source: API RP 14G, Recommended Practice for Fire Prevention and Control on Fixed Open-type Offshore Production Platforms: Upstream Segment, Fourth Edition, April 2007. Global Standards Source: API RP 49, Recommended Practice for Drilling and Well Servicing Operations Involving Hydrogen Sulfide, Third Edition, May 2001. Global Standards Source: API RP 98, Personal Protective Equipment Selection for Oil Spill Responders, First Edition, August 2013. Global Standards Source: State of Wyoming Occupational Safety and Health Rules and Regulations for Oil and Gas Well Drilling, Revised January 8, 2013. Regulations
NEMA

NEMA

Definition(s)


NEMA

National Electrical Manufacturers Association. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
NEC

NEC

Definition(s)


NEC

National Electrical Code. API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards Source: API RP 14G, Recommended Practice for Fire Prevention and Control on Fixed Open-type Offshore Production Platforms: Upstream Segment, Fourth Edition, April 2007. Global Standards
MMS

MMS

Definition(s)


MMS

Minerals Management Service, U.S. Department of the Interior. Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards Source: API RP 49, Recommended Practice for Drilling and Well Servicing Operations Involving Hydrogen Sulfide, Third Edition, May 2001. Global Standards  

MMS

Minerals Management Service. Source: Deepwater Well Control Guidelines. IADC Guidelines
MIC Ratio

MIC Ratio

Definition(s)


MIC Ratio

Minimum igniting current ratio. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards

Minimum igniting current ratio (MIC Ratio)

The ratio derived by dividing the minimum current required from an inductive spark discharge to ignite the most easily ignitable mixture of a gas or vapor by the minimum current required from an inductive spark discharge to ignite methane under the same test conditions. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
Minimum Igniting Current Ratio

Minimum Igniting Current Ratio

Definition(s)


Minimum igniting current ratio (MIC Ratio)

The ratio derived by dividing the minimum current required from an inductive spark discharge to ignite the most easily ignitable mixture of a gas or vapor by the minimum current required from an inductive spark discharge to ignite methane under the same test conditions. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards
MESG

MESG

Definition(s)


MESG

Maximum experimental safe gap. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards

Maximum experimental safe gap (MESG)

The maximum clearance between two parallel metal surfaces that has been found, under specified test conditions, to prevent an explosion in a test chamber from being propagated to a secondary chamber containing the same gas or vapor at the same concentration. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards  

Maximum experimental safe gap (MESG)

The maximum gap of the joint between the two parts of the interior chamber of a test apparatus which, when the internal gas mixture is ignited and under specified conditions, prevents ignition of the external gas mixture by flame propagation through a 25 mm (1 in.) long joint, for all concentrations of the tested gas or vapor in air. API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards
Maximum Experimental Safe Gap

Maximum Experimental Safe Gap

Definition(s)


Maximum experimental safe gap (MESG)

The maximum clearance between two parallel metal surfaces that has been found, under specified test conditions, to prevent an explosion in a test chamber from being propagated to a secondary chamber containing the same gas or vapor at the same concentration. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards

Maximum experimental safe gap (MESG)

The maximum gap of the joint between the two parts of the interior chamber of a test apparatus which, when the internal gas mixture is ignited and under specified conditions, prevents ignition of the external gas mixture by flame propagation through a 25 mm (1 in.) long joint, for all concentrations of the tested gas or vapor in air. API RP 500, Recommended Practice for Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class I, Division 1 and Division 2, Third Edition, December 2012, Global Standards

MIE

MIE

Definition(s)


MIE

Minimum ignition energy. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards

Minimum ignition energy (MIE)

The smallest amount of energy that can ignite the most easily ignitable mixture of a specific gas or vapor-in-air mixture or dust-in-air mixture. Source: API Recommended Practice 14FZ, Recommended Practice for Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class I, Zone 0, Zone 1, and Zone 2 Locations, Second Edition, May 2013. Global Standards Source: API RP 14F, Design, Installation, and Maintenance of Electrical Systems for Fixed and Floating Offshore Petroleum Facilities for Unclassified and Class 1, Division 1 and Division 2 Locations, Fifth Edition, July 2008. Global Standards